Ground Grid Installation

Ground grids are installed at a depth such that the currents flowing in from the above grade steel structures or shield wire(s) are easily dissipated into the earth. This is accomplished by:

  1. Drilling ground rods (at strategic locations) to a depth where the soil resistivity is low.
  2. Connecting the ground grid to the rods so that the grid can access the low resistivity soil.

Typically the ground grid is installed at 36” below grade while the ground rods are driven into the soil to a depth of 10 feet. These depths are approximate and vary with design standards of various electric utilities. At locations where the soil resistivity is high, ground wells are accessed.

But Why Ground?

The purpose of grounding is to prevent electric shock and to mitigate overvoltages that can damage equipment. In substations, the high voltage lines carry alternating currents. If you are familiar with Faraday’s induction principle, a time varying flux (due to alternating current) induces voltage in an adjacent conductive equipment.

This means the steel structures in and around live equipment will pose a shock hazard. Even the  fence enclosing the substation will have induced voltage when high voltage transmission lines pass overhead. It is essential to ground all above grade conductive structures to mitigate the shock hazard.

Types Of Shock Hazard In A Substation

  1. Touch Potential Hazard
  2. Step Potential Hazard

Touch Potential Hazard

As the name suggests, it is a shock hazard brought on by touching the steel structure inside the substaton. Ofcourse, this happens when the equipment you are touching is improperly grounded.

Step Potential Hazard

When there is more fault current flowing into the ground grid than the grid can dissipate, the potential of the ground rises. Scary stuff. If you try walking inside the substation (in your sneakers) during this abnormal potential rise, every step you take will zap you due to the potential difference you create between your feet.

Touch and step potential hazard can be analyzed in a grounding study using IEEE Std. 80 or IEC 479-1. A geotech survey of the substation needs to be performed to obtain the soil resistivity data to enable this study.

Summary

  1. Grounding of steel structures inside the substation is important.
  2. The ground grid should be designed to dissipate the available fault currents and mitigate other shock hazards.

* * * * *

4 Responses to Ground Grid Design- Substation Below Grade Engineering

  1. Antony Alapatt says:

    IEEE 80 puts the recommended grounding grid depth at 300-500mm (12-18inches) per Section 9.2.b)1)
    Could you clarify why you have mentioned above typical ground grid is installed 36 inches below grade.

    Another question is would it be okay to have the ground grid depth a little higher or lower in depth at select portions of a substation for convenience (Eg. if the ground grid is a little deeper near the control house to assist with the conduit entrance into the control house (to have the conduit running above the ground grid there); would that be okay.

  2. Abraar says:

    Can you please include relevant photos here and there? You are already spending so much time writing an article, why not make it visual too.

  3. Fadel Aldhaif says:

    Thank you.
    This Website helps me how to solve the per-unit system.

  4. mahendra says:

    Thanks.. very useful and easily understandable..

Leave a Reply